Explicit DHW tank type selection (Water/Thermal battery), migration to the correct type is done automatically.
Reduced compressor starts during periods of low heating demand (e.g., autumn and spring).
Improved parallel buffer support.
Fixes
Resolved an issue where certain OpenTherm thermostats showed a disconnected error due to startup delay after reboot of the heat pump.
Fixed a bug where an OpenTherm disconnected error was displayed when the space cooling control mode was set to OpenTherm despite space cooling being disabled.
Refined the OpenTherm implementation for handling relative modulation levels.
Fixed an issue on single-phase installations where the resistance heater would fail to heat the DHW tank under certain conditions.
Added a 30-second debounce filter for On/Off thermostat inputs to prevent unintended switching issues.
Fixed an issue in HP5 Duo setups where the heat pump power was incorrectly limited.